Running Induction Cooktops & Air-Con: Surge (LRA), Soft-Start & Inverter Sizing

Modified on Wed, 29 Oct at 10:23 PM

Modern caravan and off-grid travellers love the comfort of home—especially induction cooktops and air-conditioners.
But these high-draw appliances have one big catch: surge power. Understanding surge current (LRA), inverter sizing, and soft-start options ensures your system runs safely without tripping or shutting down.


⚡ 1. Understanding Surge (LRA) Power

Every motor or compressor appliance demands a brief current spike on startup.
This spike is known as Locked Rotor Amperage (LRA)—often 3 × to 8 × the running current.

ApplianceTypical Running DrawTypical Startup Surge (LRA)
1 kW Induction Cooktop~1000 W1800–2200 W for 0.5 s
1000 W Air-Con Compressor~1000 W2500–4000 W for 1–2 s
Fridge/Freezer Compressor100 W300–600 W for 1 s
Power Tools (Angle Grinder, Drill)800 W1500 W+ transient

If your inverter can’t deliver this short-term surge, it may:

  • Trip into overload protection

  • Fail to start the appliance

  • Produce audible buzzing or partial startups that stress both inverter and load


⚙️ 2. Choosing the Right Inverter Size

Step 1 – Find Running Power

Check the appliance label (or manual) for rated watts or amps.

Step 2 – Estimate Startup Surge

Multiply running power by a surge factor:

  • Induction cooktops → × 2

  • Compressor air-cons → × 3 to 5

  • Power tools → × 2 to 3

Step 3 – Select an Inverter With Sufficient Surge Rating

Most pure sine wave inverters can supply 2 × their continuous rating for 1–3 seconds.
For example:

  • A 3000 W / 6000 W pure sine inverter supports surges up to 6 kW briefly—enough for many cooktops and 1 HP air-cons.

  • A 2000 W inverter may start a 1000 W cooktop but not a 1000 W air-con without soft-start assistance.

Step 4 – Check Battery & Cable Capacity

High surge loads draw massive DC current:

At 12 V, 3000 W = 250 A (and 500 A surge!)
Use 4 AWG or larger cabling, short runs (<1 m), and appropriate ANL or MIDI fuses.
Undersized cables cause voltage sag, inverter cutoff, or heat damage.


?️ 3. The Role of Soft-Start Devices

A soft-start module limits compressor or motor inrush current by ramping voltage over a few hundred milliseconds.

Benefits:

  • Reduces LRA by 50–70 %

  • Prevents inverter overloads

  • Extends inverter and compressor lifespan

Examples:

  • Air-con Soft Starter (e.g., Micro-Air EasyStart, SoftStartRV)

  • Induction Cooktops with “Power Share” or “Eco Mode” functions

  • Variable Frequency Drives (VFD) in larger AC units

With soft-start, a 3000 W inverter can often handle appliances previously needing 5000 W.


? 4. Battery Bank & DC Source Considerations

Even with a strong inverter, voltage sag on startup can trip the unit if the battery can’t supply the amps.

  • Use LiFePO₄ batteries: high discharge (100 A + per 100 Ah cell)

  • Parallel cells for higher current capacity

  • DC bus bars to balance current evenly

  • Thick cables (≥ 25 mm²) and solid crimp lugs

If running long surges (e.g., 10 s on induction), voltage must stay above 11.5 V DC to avoid low-voltage cutout.


? 5. Real-World Example

Setup:

  • Gentrax 12 V 100 Ah LiFePO₄ × 2 (200 Ah total)

  • 3000 W / 6000 W Pure Sine Inverter

  • 1 kW Induction Cooktop

Results:
Startup ≈ 2200 W (0.5 s)
Steady ≈ 1000 W (≈ 85 A draw)

→ Runs smoothly; surge absorbed by battery + inverter reserve.
Without the dual battery bank, inverter tripped on startup.


? 6. Practical Tips

  • Turn other heavy loads off (kettle, toaster, AC) before starting an induction cooktop.

  • Pre-cool air-con on generator or mains before switching to inverter.

  • Keep battery SOC > 60 % for better surge handling.

  • In hot climates, mount inverter in a ventilated area to prevent thermal derating.

  • Use pure sine wave only—modified sine inverters cause buzzing, poor induction heating, and potential appliance damage.


✅ 7. Summary Table

ApplianceContinuous Load (W)Recommended Inverter SizeNotes
Single-zone Induction Cooktop1000 – 18003000 W / 6000 W surgeUse Eco mode or limit power to 1 kW
Caravan Air-Con 1 HP1000 – 13003000–5000 W with Soft-StartNeeds ≥ 200 Ah LiFePO₄
Compressor Fridge / Freezer60 – 150300–600 WUsually fine on small inverters
Microwave (700 W rated)1100 – 12002000 WShort bursts only

Was this article helpful?

That’s Great!

Thank you for your feedback

Sorry! We couldn't be helpful

Thank you for your feedback

Let us know how can we improve this article!

Select at least one of the reasons
CAPTCHA verification is required.

Feedback sent

We appreciate your effort and will try to fix the article