MC4 Connectors: Crimp vs Solder, IP Ratings & Common Failures

Modified on Thu, 27 Nov at 12:39 AM

MC4 connectors are the industry standard for joining 12V and 24V solar panels in caravan, camping and off-grid systems.
They are durable, weatherproof and designed to carry high current — but only when terminated correctly.

Incorrect MC4 connections are one of the most common causes of:

  • Low solar output

  • Intermittent charging

  • Panels producing “0 watts”

  • Melted connectors

  • Water ingress

  • Controller voltage drop warnings

This guide covers the correct way to terminate MC4 connectors, the difference between crimped vs soldered connections, MC4 IP67/IP68 ratings, and the most common failure points we see in customer installations.


1. What Are MC4 Connectors?

MC4 (“Multi-Contact, 4 mm²”) connectors are:

  • Locking, waterproof, DC-rated connectors

  • Standard on nearly all modern solar panels

  • Designed for solar-grade cable (usually 4mm² to 6mm² PV cable)

  • Rated for 25–30A depending on brand

  • Designed for crimped, not soldered, terminations

MC4 connectors ensure:

  • Low resistance connection

  • UV-resistant outdoor durability

  • Safe disconnection under load (when used correctly)

  • Secure polarity protection

They must be installed with the correct MC4 crimp tool to ensure reliable performance.


2. Crimp vs Solder – Which Is Better?

Crimping (Recommended)

A correct crimp forms a gas-tight, mechanically secure connection between conductor and terminal.

✔ Advantages of crimping:

  • Strong mechanical grip

  • Maintains full current-carrying capacity

  • No hot spots or resistance increase

  • Designed for solar PV cable

  • Retains MC4 waterproof rating (IP67/IP68)

  • Survives vibration (caravans, 4WD, boats)

  • Meets Australian electrical standards for DC PV systems

→ Crimping is the ONLY approved method for MC4 terminations.


Soldering (Not Recommended / Common Failure)

Soldering MC4 connectors is not compliant, unsafe, and leads to frequent faults.

✘ Problems caused by soldering:

  • Solder creeps under heat → loosens the joint

  • Creates rigid point → conductor breaks with vibration

  • Solder reduces MC4’s locking strength

  • Causes high-resistance hot spots

  • Frequently leads to melted connectors

  • Usually voids product warranty

  • Fails IP ratings (water penetrates due to capillary action)

→ Never solder MC4 terminals.
→ Solar manufacturers, MC4 manufacturers and Australian Standards all specify crimp only.


3. MC4 IP Ratings Explained (IP67 vs IP68)

Most genuine MC4 connectors are rated IP67 or IP68, meaning:

  • IP6X → dustproof

  • IPX7 → can withstand submersion in 1m water for 30 minutes

  • IPX8 → deeper submersion for extended time (varies by manufacturer)

However, these ratings only apply if the connector is terminated properly.

Common reasons the IP rating is lost:

  • Soldering instead of crimping

  • Incorrect cable diameter (too thin or too thick)

  • Missing O-rings

  • Cross-threaded locking nuts

  • Connectors not fully clicked/locked

  • Cable insulation not sealed at the gland

Once water enters an MC4, performance drops dramatically and corrosion begins within days.


4. Common MC4 Failures & How to Avoid Them

Below are the most frequent MC4 faults we see in customer installations and warranty tickets.


1. Poor Crimp / Loose Connection

Symptoms:

  • Panel shows correct voltage but low amps

  • Output drops or fluctuates

  • Connector or cable becomes warm under load

Causes:

  • Wrong crimp tool

  • Crimp wings not fully compressed

  • Terminal not seated properly

Solution:
Re-crimp with a proper MC4 ratchet crimp tool.


2. Soldered Terminals

Symptoms:

  • Intermittent power

  • Melted connectors

  • Connector separates under vibration

  • High resistance readings

Solution:
Cut off connector → strip cable → re-terminate with correct crimp.


3. Water Ingress / Corrosion

Symptoms:

  • Brown/green corrosion inside connector

  • Voltage present, but zero charging

  • MPPT shows “PV disconnected” or “Low PV input”

Causes:

  • Incomplete tightening

  • Damaged O-ring

  • Wrong cable diameter

  • Installation in low-hanging, water-prone locations

Solution:
Replace entire MC4 pair; never reuse water-damaged connectors.


4. Reverse Polarity

Symptoms:

  • Sparks when connecting

  • Controller refuses to boot

  • Blown fuse or damaged controller

Cause:
Crossed MC4 male/female or incorrect polarity labelling.

Solution:
Correct polarity is:

  • MC4 Male Plug = Positive (+)

  • MC4 Female Plug = Negative (–)
    (Some panels reverse the housing gender; always check labels.)


5. Mixing Genuine & Non-Genuine MC4 Brands

Symptoms:

  • Connectors don’t fully lock

  • Slight movement or looseness

  • Intermittent contact

Cause:
Dimensions vary between cheap/non-genuine connectors.

Solution:
Use matching, branded MC4 pairs on each connection.


6. Overheating / Melted MC4 Connectors

Symptoms:

  • Plastic deformation

  • Smell of burnt plastic

  • Connector fused together

Causes:

  • Undersized cable

  • High current through a bad crimp

  • Loose connector not fully locked

  • Soldered joint creating hot spot

Solution:
Replace connector; inspect entire cable length.


5. Correct Way to Install MC4 Connectors (Step-by-Step)

1. Strip 10–12mm of insulation

Use a sharp stripper sized for solar cable.

2. Insert conductor into MC4 metal terminal

Ensure all strands enter cleanly — no frayed strands.

3. Crimp with a PV-rated ratchet crimp tool

The crimp should be:

  • Firm

  • Symmetrical

  • Gas-tight

  • No copper visible outside the barrel

4. Slide terminal into MC4 housing

You should hear/feel a positive click when it locks.

5. Tighten the gland nut

Use MC4 spanners to achieve a water-tight seal.

6. Perform a pull test

Firmly pull the cable — it should not budge.


6. Should I Replace Old or Damaged MC4s?

Yes — any of the following symptoms require replacement:

  • Connector won’t lock

  • Water or corrosion visible

  • Melted or warped plastic

  • Soldered terminals

  • High resistance readings

  • Frayed cable

  • Loose metal terminal

A failed MC4 can cause:

  • Fire risk

  • Full system shutdown

  • Controller damage

  • Permanent loss of solar panel performance

Replacing MC4s is inexpensive and prevents major issues.


7. MC4 Compatibility with Different Solar Panels

MC4s can be used with:

  • Shingled panels

  • TOPCon

  • PERC

  • Half-cut mono panels

  • Portable folding panels

  • Flexible panels

But they must match:

  • Correct cable size

  • Correct current rating

  • Male-to-female orientation

  • Brand/type on each side

Never mix connectors from different brands on the same pair, even though they may physically fit.


8. Testing MC4 Connections

Before final installation, test each connection with a multimeter.

Voltage Test

  • Unplug the array

  • Check panel Voc (open-circuit voltage)

  • Compare with back-label specs

Continuity Test

  • Set multimeter to continuity

  • Verify positive and negative paths

  • Check for correct polarity

  • Ensure no intermittent breaks

Resistance Test

  • High resistance indicates a bad crimp or water/oxidation inside connector.


9. Frequently Asked Questions

Can I reuse old MC4 connectors?

Not recommended. Once crimped and weathered, they should be replaced.

Can MC4s be submerged?

IP67/IP68 means temporary submersion is fine, but long-term water exposure will cause failure.

Are MC4s safe on a caravan roof?

Yes — when properly crimped and UV-rated cable is used.

Can I extend solar panel leads using MC4 extension cables?

Yes — but ensure correct cable gauge (4mm² or 6mm²) to minimise voltage drop.

Why are my MC4s getting hot?

This indicates a bad crimp, mismatched connectors, excessive load or damaged wiring.


Need Help Diagnosing MC4 Issues?

If your system is showing low output, please send us:

  1. A clear photo of each MC4 connection

  2. The panel back-label

  3. Your charge controller model

  4. How the panels are wired (series or parallel)

We’ll diagnose the issue and advise the safest and most efficient repair.